From the video using an EM Sensor, you will see the discharge activities online are very few of low magnitudes from the intermittent pulses seen. However, when the sensor is moved to the next 6kV switchgear panel, more pulses are seen at high magnitude. Further analysis confirm the presence of CORONA discharges at an Early Stage.

Client need to monitor quarterly to gauge accurately the deterioration before service Shutdown in a year time
.

 


June 2011
Partial Discharge Condition in a 6kV switchgear (video) .... more


 


 